Palmetto Energy Center

80 MW solar + 40 MW / 160 MWh BESS
Owned
Kinney County, TX

Last updated: Apr 30, 2026 · COD: Feb 2024

Daily GenerationSCADA
478 MWh

30-day avg (expected: 492 MWh)

AvailabilitySCADA
96.4%

30-day (owned, no SLA)

Performance RatioComputed
82.1%

Weather-adjusted, 30-day

Generation GapComputed
-2.8%

vs weather-adjusted model

SLA StatusContract
N/A (Owned)

No contractual exposure

Revenue ImpactComputed
No exposure

Owned asset

Work OrdersCMMS
3 open (1 critical)

BESS warranty review

DispatchField Ops
HVAC-3 swap May 3

Vendor scheduled

AI Observations

3

SOH at 91.8% — outside expected range at 18 months

BatteryCritical

Trending toward 80% threshold by month 42 vs expected 84+. Warranty review needed.

Confidence High·
BMSCapacity test

HVAC-3 failure on Apr 18 — rack 3 shows 0.4% extra fade

ThermalConcern

Rack 3 ran >35°C for 6h. Derated until HVAC replacement May 3.

Confidence High·
BMSHVAC log

RTE declining 0.3%/month — 6× expected rate

PerformanceWatch

Correlates with cell resistance rise in racks 3, 7, 12.

Confidence Medium·
Computed RTECell resistance

Battery Status

State of Health91.8%Expected: 96% at 18moBMS
Round-Trip Eff83.4%Baseline: 89.1%Computed
Capacity Fade8.2%Expected: 2-4% at 18moComputed
Equivalent Cycles412 EFCSince COD (18mo)BMS
Thermal Events (30d)2HVAC-3 + cell anomalySCADA
Availability94.2%30-daySCADA

SOH Trend — Actual vs Warranty Curve

State of Health since COD vs warranted degradation curve. Gap widening since month 12.

Rack Temperature Heatmap

16 battery racks. Rack 3 elevated due to HVAC-3 failure (Apr 18).

Rack 1
26°C
Rack 2
28°C
Rack 3
38°C
Rack 4
27°C
Rack 5
24°C
Rack 6
26°C
Rack 7
28°C
Rack 8
25°C
Rack 9
27°C
Rack 10
24°C
Rack 11
26°C
Rack 12
33°C
Rack 13
25°C
Rack 14
27°C
Rack 15
24°C
Rack 16
26°C

AI
AI Assistant

Generation Gap by Site
vs model
Longleaf
-18.4%
Bluestem
-7.4%
Cardinal
-5.2%
Sundance
-4.1%
Palmetto
-2.8%
Bay Tree
-2.4%
Shoe Creek
-1.2%